THÔNG SỐ KỸ THUẬT CỦA e430/ e4031
- Model e430
POWER SUPPLY |
Internal | via backplane |
Power dissipation | 3 W max | |
CONNECTIONS |
Rack | Card-edge |
I/O Ports | 2 polarized plug-in connectors, male,
24 pin (2 rows of 12 pins) * |
|
DISPLAY ELEMENTS | Diagnostic | Alarm red LED
Yellow LED for power potentiometer |
ANALOG INPUT | Number | 6, configurable as single-ended voltage 0…10 V, single ended volt-
age ±10 V, potentiometer or current 0…20mA |
ANALOG INPUT IN VOLTAGE 0…10 V |
Max number | 6 |
Type | Single-ended voltage 0…10 V | |
Input filter | Low-pass, 3rd order
Cut-off frequency: 100 Hz, 1 kHz, 10 kHz selectable via software |
|
Input impedance | > 1 MΩ | |
Sampling time
(for all channels) |
< 250 μs | |
Output format | Type: UINT
Resolution: 14 bit (0 … 16 384) LSB: 0,61 mV |
|
Max error @ 25 °C | 0,5% full scale | |
Protections | Over-voltage: max 1 kV for 1 ms | |
Electrical isolation | Channel – channel: no
Channel – bus CPU: 2 kV |
|
ANALOG INPUT IN VOLTAGE ±10 V |
Max number | 6 |
Type | Single-ended voltage ±10 V | |
Input filter | Low-pass, 3rd order
Cut-off frequency: 100 Hz, 1 kHz, 10 kHz selectable via software |
|
Input impedance | > 1 MΩ | |
Sampling time
(for all channels) |
< 250 μs | |
Output format | Type: INT
Resolution: 15 bit (-16 384 … +16 384) LSB: 0,61 mV |
|
Max error @ 25°C | 0,5% full scale | |
Protections | Overvoltage: max 1 kV per 1 ms | |
Electrical isolation | Channel – channel: no
Channel – bus CPU: 2 kV |
|
ANALOG INPUT IN CURRENT 0…20 mA |
Max number | 6 |
Type | Current 0…20 mA | |
Input filter | Low-pass, 3rd order
Cut-off frequency: 100 Hz, 1 kHz, 10 kHz selectable via software |
|
Input impedance | 100Ω, 0,1% | |
Sampling time
(for all channels) |
< 250 μs | |
Output format | Type: UINT
Resolution: 14 bit (0 … 16 384) LSB: 1,22 mA |
|
Max error @ 25 °C | 0,3% full scale | |
Protections | Overvoltage: max 1 kV per 1 ms | |
Electrical isolation | Channel – channel: no
Channel – bus CPU: 2 kV |
ANALOG INPUT POTENTIOMETER |
Max number | 6 |
Type | Potentiometer 2 kΩ min | |
Transducer power supply | On card, 10 V – 100 mA max | |
Input filter | Low-pass, 3rd order
Cut-off frequency: 100 Hz, 1 kHz, 10 kHz selectable via software |
|
Input impedance | > 1 MΩ | |
Sampling time
(for all channels) |
< 250 μs | |
Output format | Type: UINT
Resolution: 14 bit (0 … 16 384) LSB: 0,61 mV |
|
Max Error @ 25 °C | 0,5% full scale | |
Protections | Overvoltage: max 1 kV per 1 ms | |
Electrical isolation | Channel – channel: no
Channel – bus CPU: 2 kV |
|
THERMOCOUPLE INPUT |
Number | 8 |
Type | Thermocouple J, K, S, N, T, E, B, R, L
Differential voltage 0…60 mV |
|
Connection type | 2 wires, for isolated and non-isolated probes | |
Bandwidth | 1 Hz | |
Input impedance | > 1 MΩ | |
Sampling time
(for all channels) |
< 12 ms | |
Resolution | 0,1 °C | |
Max error @ 25 °C | 0,5% full scale | |
Thermocouple use interval (scale) | J: 0 … 1000 °C
K: 0 … 1300 °C R: 0 … 1750 °C S: 0 … 1750 °C T: -200 … 400 °C E: -100 … 750 °C B: 0 … 1820 °C (Err. max 0.5% f.s. for Temp. >300°C) L: 0 … 800 °C N: 0 … 1300 °C |
|
Temperature compensation | Internal | |
ANALOG OUTPUT |
Number | 4 |
Type | Single-ended voltage ±10 V | |
Max output current | 20 mA | |
Refresh time | 1 ms | |
Settling time | < 200 µs | |
Output format | Type: INT
Resolution: 14 bit (-8 192 … +8 192) LSB: 1,22 mV |
|
Error max @ 25 °C | 0,3% full scale | |
Protections | Short circuit Overload: I ≥ 25 mA
Max overvoltage 1 kV per 1 ms |
|
Electrical isolation | Channel – channel: no
Channel – bus CPU: 2 kV |
|
AMBIENT CONDITIONS |
Operating temperature | 0 … +50 °C (as per IEC 68-2-14) |
Storage temperature | -20 … +70 °C (as per IEC 68-2-14) | |
Relative humidity | max 95% RH non-condensing (as per IEC 68-2-3) | |
ASSEMBLY | On rack, with snap hooks | |
PROTECTION LEVEL | IP20 | |
WEIGHT | 0,15 kg |
Model e4301
POWER SUPPLY |
Internal | via backplane |
Power dissipation | 8 W max | |
CONNECTIONS |
Rack | Card-edge |
I/O Ports | 2 polarized plug-in connectors, male, 24 pin (2 rows of 12 pins) * | |
DISPLAY ELEMENTS |
Diagnostic | 20 Green LEDs: Outputs status
1 Red LED: Alarm 3 Yellow LEDs: Power Supply |
DIGITAL OUTPUT |
Number | 20 |
Composition | 2 Groups of 8 outputs and 1 group of 4 outputs | |
Type | current-emission | |
Rated voltage | 24 VDC ±25% | |
Max output current | Single output : 0,5 A Group of 20 outputs: 10 A | |
Max switching frequency | 100 Hz | |
Switching delay | 0 à1: 15 μs
1 à0: 40 μs |
|
Protections | Short circuit
Overload: I ≥ 0,7 A (as per IEC 61131), trip time:500 ms min Overtemperature |
|
Electrical isolation | Channel – channel: no Channel – bus CPU: 2 kV | |
THERMOCOUPLE INPUT |
Number | 12 |
Type | ThermocoupleJ, K, S, N, T, E, B, R, L Differential voltage 0…60 mV | |
Connection type | 2 wires, for isolated and non-isolated probes | |
Bandwidth | 1 Hz | |
Input impedance | > 1 MΩ | |
Sampling time (for all channels) | < 100 ms | |
Resolution | 0,1 °C | |
Max error @ 25 °C | 0,5% full scale | |
Thermocouple use interval (scale) | J: 0 … 1000 °C
K: 0 … 1300 °C R: 0 … 1750 °C S: 0 … 1750 °C T: -200 … 400 °C E: -100 … 750 °C B: 0 … 1820 °C (Err. max 0.5% f.s. for Temp. >300°C) L: 0 … 800 °C N: 0 … 1300 °C |
|
Temperature compensation | Internal | |
AMBIENT CONDITIONS |
Operating temperature | 0 … +50 °C (as per IEC 68-2-14) |
Storage temperature | -20 … +70 °C (as per IEC 68-2-14) | |
Relative humidity | max 95% RH non-condensing (as per IEC 68-2-3) | |
ASSEMBLY | On rack, with snap hooks | |
PROTECTION LEVEL | IP20 | |
WEIGHT | 0,13 kg | |
CE STANDARDS |
EMC
(electromagnetic compatibility) |
Conforms to Directive 2004/108/CE EMC Emission: EN 61000-6-4
EMC Immunity: EN 61131-2, EN 61000-4-2, EN 61000-4-3, EN 61000- 4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11 |
LV
(low voltage) |
Conforms to Directive 2006/95/CE Safety LVD: EN 61010-1 | |
* Female connectors not supplied. See accessories for order Model Number. |