Mô tả
THÔNG SỐ KỸ THUẬT CỦA KFD2-STC5-Ex2
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Systematic capability (SC) | SC 3 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 18 … 30 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | ≤ 1.4 W at maximum load | |
Power consumption | ≤ 2.6 W at maximum load | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2-, 3; 4+, 5-, 6 | |
Input signal | 0/4 … 20 mA | |
Open circuit voltage/short-circuit current | terminals 1+, 3; 4+, 6: 23 V / 25 mA | |
Input resistance | max. 265 Ω terminals 2-, 3; 5-, 6 , max. 330 Ω terminals 1+, 3; 4+, 6 | |
Available voltage | ≥ 16 V at 20 mA ; ≥ 20 V at 4 mA , terminals 1+, 3; 4+, 6 | |
Output | ||
Connection side | control side | |
Connection | terminals 7+, 8-, 9-; 10+, 11-, 12- (sink) terminals 7-, 8+, 9+; 10-, 11+, 12+ (source) see additional information | |
Load | 0 … 600 Ω | |
Output signal | 0/4 … 20 mA (overload > 25 mA) | |
Ripple | max. 50 µA rms | |
External supply (loop) | 2 … 30 V DC | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F), 0/4 … 20 mA ≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage | |
Influence of ambient temperature | ≤ 0.25 µA/K | |
Frequency range | field side into the control side: band width with 1 Vpp signal 0 … 7.5 kHz (-3 dB) safe area to hazardous area: band width with 1 VSS signal 0.3 … 7.5 kHz (-3 dB) | |
Settling time | 200 µs | |
Rise time/fall time | 100 µs | |
Galvanic isolation | ||
Output/power supply | functional insulation, rated insulation voltage 50 V AC | |
Output/Output | functional insulation, rated insulation voltage 50 V AC | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | UL 61010-1:2012 | |
Ambient conditions | ||
Ambient temperature | -20 … 60 °C (-4 … 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 200 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | CML 17 ATEX 2031X | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
Supply | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Equipment | terminals 1+, 3-; 4+, 6- | |
Voltage Uo | 26.2 V | |
Voltage Uq | 27.25 V | |
Current Io | 93 mA | |
Power Po | 634 mW | |
Equipment | terminals 2-, 3+; 5-, 6+ | |
Voltage Ui | 30 V | |
Current Ii | 115 mA | |
Power Pi | max 1 W | |
Voltage Uo | 2 V | |
Current Io | 8.5 mA | |
Power Po | 4.3 mW | |
Equipment | terminals 1+, 2/3-; 4+, 5/6- | |
Voltage Uo | 26.2 V | |
Voltage Uq | 27.25 V | |
Current Io | 115 mA | |
Power Po | 784 mW | |
Certificate | CML 17 ATEX 3030X | |
Marking | II 3G Ex ec IIC T4 Gc | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V | |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11:2007, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 | |
International approvals | ||
UL approval | E106378 | |
Control drawing | 116-0439 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx CML 17.0016X | |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
---|---|
ECLASS 11.0 | 27210119 |
ECLASS 10.0.1 | 27210119 |
ECLASS 9.0 | 27210119 |
ECLASS 8.0 | 27210119 |
ECLASS 5.1 | 27210119 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
Đánh giá
Chưa có đánh giá nào.