THÔNG SỐ KỸ THUẬT CỦA KFD2-ELD-Ex16
| Product Description | ||
|---|---|---|
| 24 V DC | ||
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Rail or terminals 44+, 45- | |
| Rated voltage | 20 … 30 V DC | |
| Ripple | ≤ 10 % | |
| Rated current | ≤ 50 mA | |
| Input | ||
| Connection side | field side | |
| Connection | intrinsically safe: terminals 1 … 16 non-intrinsically safe: terminals 28, 29 | |
| Ground connection | terminal 17 | |
| Rated values | 5 Vpp, 0.1 mA; rectangular | |
| Function | Test input: 24 V DC / 5 mA; non-polarized | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 19, 20, 21 | |
| Output | signal ; relay | |
| Contact loading | 253 V AC/2 A /cos φ > 0.7; 40 V DC/2 A resistive load; | |
| Mechanical life | 107 switching cycles | |
| Transfer characteristics | ||
| Response delay | ≤ 50 s | |
| Galvanic isolation | ||
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 260 g | |
| Dimensions | 60 x 119 x 115 mm (2.4 x 4.7 x 4.5 inch) , housing type D2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-type examination certificate | TÜV 00 ATEX 1585 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Voltage | 7.2 V | |
| Current | 1.7 mA | |
| Power | 3 mW | |
| Supply | ||
| Maximum safe voltage | 40 V DC (Attention! The rated voltage can be lower.) | |
| Collective error message | ||
| Maximum safe voltage | 40 V (Attention! The rated voltage can be lower.) | |
| Galvanic isolation | ||
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
| General information | ||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 11.0 | 27210190 |
| ECLASS 10.0.1 | 27210190 |
| ECLASS 9.0 | 27210190 |
| ECLASS 8.0 | 27210190 |
| ECLASS 5.1 | 27210121 |
| ETIM 8.0 | EC001485 |
| ETIM 7.0 | EC001485 |
| ETIM 6.0 | EC001485 |
| ETIM 5.0 | EC001485 |




II (1)G [Ex ia Ga] IIC