Mô tả
THÔNG SỐ KỸ THUẬT CỦA KFA6-DU-Ex1.D
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Supply | ||
| Connection | terminals 23, 24 | |
| Rated voltage | 230 V AC ± 10 % | |
| Rated current | 15 mA | |
| Power consumption | 4 VA | |
| Input | ||
| Connection side | field side | |
| Connection | Input I: terminals 1+, 3- ; input II: terminals 13+, 14- | |
| Input I | acc. to EN 60947-5-6 (NAMUR), see manual for electrical data | |
| Open circuit voltage/short-circuit current | 8.2 V / 10 mA | |
| Switching point/switching hysteresis | 1.2 … 2.1 mA / approx. 0.2 mA | |
| Pulse duration | min. 75 µs / 1 ms see instruction manuals; the maximum input frequency has to be observed. | |
| Input frequency | 0 … 80 Hz , pulse divider 0 … 1 kHz | |
| Line fault detection | breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA | |
| Input II | reset | |
| Active/Passive | I > 3 mA / I < 1.5 mA | |
| Open circuit voltage/short-circuit current | 12 V / 3.5 mA | |
| Pulse duration | min. 10 ms | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 ; output II: terminals 19+, 20- | |
| Output I | signal , Relay output | |
| Contact loading | 253 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Output II | signal , electronic unit, isolated | |
| Contact loading | 40 V / 50 mA | |
| Energized/De-energized delay | after rising input flank 3 ms ; after falling input flank 2 ms | |
| Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA) | |
| Transfer characteristics | ||
| Input I | ||
| Resolution | < 0.1 % of the set value, min. 10 ms | |
| Accuracy | 2 ms | |
| Influence of ambient temperature | 0.003 %/K (50 ppm) | |
| Galvanic isolation | ||
| Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output I/power supply and reset | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output II/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Output II/reset | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff | |
| Reset/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-type examination certificate | TÜV 99 ATEX 1408 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Supply | ||
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) | |
| Input I | terminals 1+, 3-: Ex ia | |
| Voltage Uo | 10.1 V | |
| Current Io | 13.5 mA | |
| Power Po | 34 mW (linear characteristic) | |
| Input II | terminals 13+, 14- non-intrinsically safe | |
| Maximum safe voltage Um | 40 V (Attention! The rated voltage can be lower.) | |
| Output I | terminals 10, 11, 12 non-intrinsically safe | |
| Contact loading | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
| Maximum safe voltage | 253 V (Attention! The rated voltage can be lower.) | |
| Output II | terminals 19+, 20- non-intrinsically safe | |
| Maximum safe voltage | 40 V (Attention! The rated voltage can be lower.) | |
| Certificate | TÜV 02 ATEX 1885 X | |
| Marking | II 3G Ex nA nC IIC T4 Gc | |
| Output I | ||
| Contact loading | 50 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
| Galvanic isolation | ||
| Input I/other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 16-538FM-12 | |
| UL approval | E223772 | |
| IECEx approval | ||
| IECEx certificate | IECEx TUN 03.0000 | |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I | |
| General information | ||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 11.0 | 27210121 |
| ECLASS 10.0.1 | 27210121 |
| ECLASS 9.0 | 27210121 |
| ECLASS 8.0 | 27210121 |
| ECLASS 5.1 | 27210121 |
| ETIM 8.0 | EC001485 |
| ETIM 7.0 | EC001485 |
| ETIM 6.0 | EC001485 |
| ETIM 5.0 | EC001485 |
| UNSPSC 12.1 | 32101514 |




II (1)G [Ex ia Ga] IIC
Đánh giá