Description
Bảng thông số kỹ thuật của cảm biến CCB10-30GS55-N1-V1
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NAMUR | |
| Rated operating distance | 10 mm | |
| Installation | flush | |
| Output type | 2-wire | |
| Nominal ratings | ||
| Installation conditions | ||
| A | 0 mm | |
| B | 0 mm | |
| C | 20 mm | |
| F | 60 mm | |
| Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | |
| Operating voltage | 5 … 15 V | |
| Switching frequency | 0 … 50 Hz | |
| Reverse polarity protection | reverse polarity protected | |
| Current consumption | ||
| Measuring plate not detected | ≤ 1.5 mA | |
| Measuring plate detected | ≥ 2.5 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1134 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Compliance with standards and directives | ||
| Standard conformity | ||
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
| Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 | |
| Approvals and certificates | ||
| ATEX approval | ||
| Equipment protection level Ga | BVS 13 ATEX E 074 X | |
| Equipment protection level Da | BVS 13 ATEX E 074 X | |
| ETL approval | cETLus | |
| Ambient conditions | ||
| Ambient temperature | -20 … 70 °C (-4 … 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector plug M12 x 1 , 4-pin | |
| Housing material | Stainless steel 1.4305 / AISI 303 | |
| Sensing face | PTFE | |
| Degree of protection | IP67 | |
| General information | ||
| Use in the hazardous area | see instruction manuals | |
Classifications
| System | Classcode |
|---|---|
| ECLASS 11.0 | 27270102 |
| ECLASS 10.0.1 | 27270102 |
| ECLASS 9.0 | 27270102 |
| ECLASS 8.0 | 27270102 |
| ECLASS 5.1 | 27270102 |
| ETIM 8.0 | EC002715 |
| ETIM 7.0 | EC002715 |
| ETIM 6.0 | EC002715 |
| ETIM 5.0 | EC002715 |
| UNSPSC 12.1 | 39121550 |




Reviews