TECHNICAL DATA OF ADV200
ADV200 | ADV200 WA – ADV200 SP | |
Control algorithm | Field Oriented Control | |
Motor type | Asynchronous / Synchronous | Asynchronous |
Analog inputs | 2 two-pole (Voltage/Current) | |
Analog outputs | 2 two-pole (1 voltage or current, 1 voltage) | |
Digital inputs | 6 (PNP / NPN) | |
Digital outputs | 4 (PNP / NPN) , (2 static and 2 relay) | |
Overload | Heavy: Async. = 150% * In (1’ every 5’), 180% * In (for 0,5”); Sync.=160% * In (1’ every 5’), 200% * In (for 3”) Light: Async. and Sync.=110% * In (1’ every 5’) | Light: 110% * In (1’ every 5’) Heavy: 150% * In (1’ every 5’); 180% * In (0,5” every 5’) |
Serial communication | Standard: RS485 with Modbus RTU. Optional: DeviceNet, Profibus DP, CANopen®, GDNet, Ethercat, Ethernet IP | |
EMI filter and Choke | Integrated | |
Programming keypad | Standard Integrated; on request external keypad. | |
Integrated PLC | Motion Drive Programmable Logic Controller, standard IEC61131-3 , 5 languages) | |
Working temperature | -10…+40°C (32°…104°F) | |
Markings | CE |
Sizes | ADV200 | ADV200 WA – ADV200 SP | ||
MODELS | Power of asynchronous motor in heavy duty | MODELS | Power of asynchronous motor in light duty | |
3 | ADV2075-…-4-E54 | 7.5 kW | ADV200-..-2110-…-4-E54 | 11 kW |
3 | ADV2110-…-4-E54 | 11 kW | ADV200-..-2150-…-4-E54 | 15 kW |
3 | ADV3150-…-4-E54 | 15 kW | ADV200-..-3185-…-4-E54 | 22 kW |
3 | ADV3220-…-4-E54 | 22 kW | ADV200-..-3300-…-4-E54 | 30 kW |
4 | ADV4300-…-4-E54 | 30 kW | ADV200-..-4370-…-4-E54 | 37 kW |
4 | ADV4370-…-4-E54 | 37 kW | ADV200-..-4450-…-4-E54 | 45 kW |
4 | ADV4450-…-4-E54 | 45 kW | ADV200-..-4550-…-4-E54 | 55 kW |
5 | ADV5550-…-4-E54 | 55 kW | ADV200-..-5750-…-4-E54 | 75 kW |
5 | ADV5750-…-4-E54 | 75 kW | ADV200-..-5900-…-4-E54 | 90 kW |
5 | ADV5900-…-4-E54 | 90 kW | ADV200-..-51100-…-4-E54 | 110 kW |