Description
Overview
3850T Multifunction controller is an all-in-one device. It combines precision PID controllers, secure datalogging, batch reporting, Set Point Programmer (Ramp & Soak), and powerful function block that will allow customized programs with sequence control configurability. The brilliant 7” touch graphic interface makes extremely clear the visualization of process parameters. This technology also provides the capability, from the front of the controller, to be configured without the need of connected PC. The 3850T meets the high accuracy standards of the Aerospace and Automotive Industries with CQI9 and AMS2750.
PID control Loops
3850T can control up to 16 individual PID loops. The flexibility of the 3850T allows the user to utilize a variety of advanced control loop functions. These range from single loop, proportional or motorized valve, ratio control, and cascade control.
The 3850T has multiple tuning methods to give the user precise control over the process. This will ensure stable and accurate temperature control for applications with critical heat demands or fast processes.
Data Logger and Batch report
The Data Logger function, combined with the Real Time Clock stores process data, IN/OUT signals and alarms status in an open file (.CSV format) or encrypted file. The minimum data sampling frequency is 1 second. The batch report option lets you to associate the archived data with a specific batch code reference. The flexibility of the 3850T data format will allow the user to create customized, production and quality reports.
DataLog Utility PC is available for an easy management of all archived data, allows manually or automatically copy, and delete files via an Ethernet network. Data stored on PC can be displayed in trend chart format or a spreadsheet (Excel type) or exported as CSV or PDF files.
Set Point Programmer (Ramp & Soak)
3850T provides an advanced Set Point programmer for the user to create control profiles with ramp, soak, hold, and event In/Out functions for each steps. The multiple process can be setup so that each zone can have synchronize time based or asynchronous times. Guaranteed Soaks, multiple event outputs for auxiliary control can be managed in the Programmer.
GETlogic
Gefran’s GETlogic is an optional programming package on the 3850T controller. GETlogic is part of the GF_Express Tool available for download from Gefran’s website. GETlogic combines logic functions and mathematical functions allowing the user to create customized sequence control with the combined use of advanced process control functions.
The 3850T as an all-in-one device, takes high level process control with math and integrates logic functions. It is now possible with the creation of virtual control channels, with delays, timers, sequence control, logic functions, mathematical functions, along with the precise PID control allowing the user to combine all advanced functions into one 3850T solution.
Custom interface GETview
GETview is also in Gefran’s GF_Express software. GETView allows the user to create graphic customized pages specific to the application. GETview, allows the user to design a dynamic graphic interface that will simplify and make clear the process interactions on the plant floor. Gefran’s includes a graphic symbol library to aid in the development of the customized views. There are easy links to associate the graphic symbols to the controller variables.
GF Express with GETview & GETlogic
GF Express is Gefran’s configuration tool for all of their micro-processor configured products. GETView and GETlogic are parts of the configuration tool for use with the 3850T.
Remote service & Security
The 3850T has several levels of password and security available. These are available for the user to protect the device from unauthorized access or use.
When needed or desired the 3850T will support a remote VNC server service that can by a PC, Tablet, or Smart Phone. This will allow viewing & editing from local or remote locations. The security levels for local access also apply to remote access. The remote service can be used for diagnostics and process views to aid production up time and troubleshooting down equipment.
Technical data of 3850T
OPERATOR INTERFACE | ||
DISPLAY | Type | TFT Touch Screen with 4-wire resistive type technology |
View area | Diagonal: 7” Dimensions (L × H): 152 × 90 mm (5.98” x 3.54”) | |
Lighting | Back lit with LED, duration 50.000 hours @ 25 °C (77 °F) | |
Resolution (pixel) | 800 × 480 (WVGA) | |
Colors | 262,000 | |
Max brightness | 240 cd/m2 | |
Contrast | 1000:1 | |
View angle | Horizontal: 60° Vertical: +45° … -60° | |
KEYBOARD | Number of keys: 10 (of which 3 programmable) Type: mechanical | |
CONTROL FUNCTIONS | ||
LOOP (Regulation) | Type | Single loop; Cascade (2 consecutive PID: PID1-PID2, PID3-PID4 …); Ratio; Valve |
PID | Number: 16 max Parameter groups: 10 max | |
Regulation type | PID ON/OFF Single action heat or cool Double action heat or cool | |
Control output | Type: continuous (0… 100%) or ON/OFF with PWM modulation. Cycle time: constant or optimised (Burst Firing) | |
Valve control | Open/close for floating type motorized valve Open/close for motorized valve with feedback (potentiometer position control) | |
Sampling time | 25 ms | |
Tuning | Automatic Self Tuning algorithms. | |
Alarms | Number: max 4 associated with each PID Type: maximum, minimum, symmetric, absolute/relative | |
SETPOINT PROGRAMMER | Programmer type | Synchronous and asynchronous setpoint programs Single-segment setpoint or ramp + maintenance profile Integrated function blocks |
Program profile | From 1 to 4 synchronous profiles | |
Program | Max number of programs: 250 Maximum number of programs running at the same time: 8 Available commands: START, HOLD/PAUSE, RESET, END, SKIP Status outputs: RUN, READY,END, HOLD | |
Segments | Setting: time segments (dd:hh / hh:mm / mm:ss) or gradient con- figuration Maximum number of segments per program: 50 Maximum number of ramps and holds per program: 100 (50 ram- ps – 50 holds) High/low limit threshold configurable for each segment PID group activation for each segment | |
IN profile events | Max number of settable IN events: 16 Acknowledged events: digital IN-resource, digital OUT, system merker | |
OUT profile events | Max number of settable OUT events: 16 ON/OFF while running the profile segment Events acknowledged: digital OUT resource, logic operation, programmer status | |
Simplified configurability | Template Configuring and running the same program on several PIDs simul- taneously | |
HBB alarm | Alarm range configuration per single segment High/low range setpoint |
GETLogic | Scope | Sequential execution of logical and mathematical instructions |
Running sequences | 1 for each program (max 8) + 1 global always active | |
Function blocks | Max number per program: 400 | |
Logic function blocks | AND, OR with default logic patterns Set/Reset, Reset/Set Rising edge, trailing edge | |
Timer function blocks | Excitation delay timer (TON) De-energising delay timer (TOFF) Flip/flop timer | |
Counter function blocks | Increasing counter Decreasing counter | |
Basic mathematical function blocks | + , – , × , : , average, minimum value, maximum value, square root, base 10 logarithm, natural base A logarithm, and raised to the power A, A raised to the power B | |
Special mathematical function blocks | Max peak, minimum peak, hold of a value, average of 2 values, minimum/maximum limit of a value | |
Special mathematical function blocks | Selection between two values Greater/Lesser/Equal/Greater- Equal/Lesser-Equal/Different | |
Process function blocks | F0 (sterilisation coefficient) | |
Resources for mathematics operators | Analog IN/OUT, SP controller, System Log/Real data | |
Resources for logical operators | Digital In/Out, Alarm Status, System Merker | |
DATA LOGGER | Scope | Continuous configured data recording |
Recordable values | Max number of analog values: 50 Max number of digital events: 50 | |
Sampling | Sampling interval: 1 s … 1 h Sampling mode: single record with time information (date/time) and values/events/actions detected Closing the sequential log file: automatic every hour/day/week (configurable) | |
Data storage | File format: CSV Data file encryption: optional Log file name with close date/time indication Storage media: internal memory File export: manual via USB key or manual/automatic via Ethernet via Gefran – DataLog Utility PC application – Report Utility | |
Graphic display | Graph: stored log data trend Max number of viewable curves: 8 Data selection by association: 8 curves Single curve scaling Available functions: enable single curve, full scale selection, zoom +/-, scroll +/- and cursor | |
PRODUCTION REPORT (Batch report) | Scope | Synchronous recording when running the program profile |
Recordable values | Max number of analog values: 50 Max number of digital events: 50 Batch name/description (selectable) Running profile data (selectable) | |
Sampling | Sampling interval: 1 s … 1 h Sampling mode: single record with time information (date/time) and values/events/actions detected | |
Data storage | File format: CSV Data file encryption: optional Log file name with close date/time indication and Job ID reference (optional) Storage media: internal memory File export: manual via USB key or manual/automatic via Ethernet via Gefran – DataLog Utility PC application – Report Utility | |
Graphic display | Graph: stored log data trend Max number of viewable curves: 8 Data selection by page: 8 curves Single curve scaling Available functions: enable single curve, full scale selection, zoom +/-, scroll +/- and cursor |
TREND GRAPH REAL TIME | Scope | Continuous recording of data configured without archiving |
Recordable values | Max number of analog and digital values: 24 | |
Graphic display | Max number of viewable curves by page: 24 Number of samples: 5,000 Single curve scaling Available functions: enable single curve, full scale selection, zoom +/-, scroll +/- and cursor | |
PROGRAM RECIPE | Data file | Programmer profile segment/event configuration Synchronised programmer logic operations Synchronised programmer mathematics functions DataLog/Batch data configuration |
References | Descriptive name and ID code (easy loading and activation) | |
Data import and export | Via USB key | |
CONFIGURATION RECIPE |
Types | System: number of clocks, home page, program modes … PID: all single PID configuration parameters GETView: custom page configuration InOut: analog channel range, decimal point configuration, unit of measure configuration Messages: custom text list |
Data import and export | Via USB key | |
GETView | Scope | Configure custom graphic pages directly from the controller panel |
Number of customisable pages | 10 max | |
Components | Available types: • Led: digital variable with color/text/image change • Notes: default text display • Text: fixed text display • Edit text: text view and edit • Progress: display a value as a bar (vertical/horizontal) • Data display: display of a numeric value • Data edit: view and edit a numeric value • Button: change the status of a digital value with status di- splay (color/text/image) and change mode selection (momen- tary/toggle) • System: page change function with default list selection Maximum number of components of the same type per page: • Text (Note, Text, Edit text) and numerical (Display date, Edit date): max 40 • Key: max 20 • LED: max 20 • Progress: max 16 • Image: max 10 • System: max one link of each type | |
Available functions | Add a new component Edit component parameters Delete a component Move a component Multiple component selection for move or delete Align multiple components left Align multiple components top | |
Image functions | Image conversion tool from the most popular graphic file formats Image file import and export via USB key | |
WEEKLY CLOCK | Scope | Event (ON/OFF) on a weekly or daily basis |
Function | Configure ON/OFF event status by single day of the week Event time settings in hh:mm Enable the weekly clock Enable weekly repetition | |
Number | 4 max |
MULTILINGUAL | Scope | Change message language |
Function | UNICODE support Custom message translation File import and export via USB key | |
Available languages | Italian (ITA), English (ENG), French (FR) | |
DIAGNOSTICS | Scope | Controller operating status |
PID loop | Short circuit or probe opening Interrupted or partially interrupted load (HB alarm) | |
Communication | Communication status between panel and I/O modules Communication error alarm | |
I/O modules | Signal status and single channel values | |
System | Disk Full Alarm | |
ALARMS | Number | 254 max |
Function | Alarm message customisation ACK/no ACK selection Real alarm display priority order level settings | |
VARIABLES |
Available types | Merker (boolean) Retain Merker (boolean) Register (32 bit with sign) Retain Register (32 bit with sign) Real (32 bit) Retain Real (32 bit) String (text message) Function |
Number | max 256 per type | |
USERS | Levels | Number of default levels: 3 (operator, level 0; Maintenance, level 1; OEM manufacturer, level 2) |
Safety | Password Automatic timed logout at operator level | |
Internal functions | Add new user | |
REMOTE CONNECTIVITY | Modbus TCP | Modbus TCP Slave HMI/SCADA/DCS Data exchange systems |
VNC | Remote page standard interface Remote machine maintenance | |
REPORT UTILITY (external tool) | Connection | Ethernet Server NTP (option) |
Function | Remote DataLog and batch management Encrypted DataLog and batch file decryption Manual controller file copy or deletion Timer Configuration for automatic controller file copy or deletion Data trend graphic display (with graph zoom and scroll) Data display in spreadsheet mode Data export in .CSV or .PDF format | |
GF_eXpress (PC configuration) | Connection | Ethernet |
Function | PID controller configuration read and write Graphic display and setting of parameters useful for Programmer functions Logic and mathematics operation settings and display Creating custom graphic pages | |
NON-VOLATILE MEMORY | Type | FRAM |
Capacity | 32 kB retentive variables | |
Write | Max number: > 1012 cycles Retention: > 10 years @ 55 °C (131 °F), > 55 years @ 35 °C (95 °F) |
GENERAL DATA | ||
VOLTAGE | Operating voltage | 24 VDC ±25% |
Current absorption | 300 mA max | |
Dissipated power | 8.5 W max | |
Protections | For polarity exchange For short circuit | |
Connection | Removable 3-pin polarised connector Screw terminals, max 2,5 mm2 (0.0038 in2 ) (13 AWG) cable sec- tion | |
BUFFER BATTERY | Type | Ml2032, not replaceable |
Specifications | Rechargeable Li-Al, 3 V 65 mAh | |
Duration | 10 years. High temperatures can reduce battery life. | |
Power reserve in the absence of current | > 20 months | |
Ethernet (ETH) | Connector: RJ45 Speed: 10 / 100 Mbit/s Signals: Green LED = connection, yellow LED = data transfer Protocols: FTP (File Transfer Protocol), Modbus TCP/IP Slave | |
USB | Connector: type A Type: Host Port Version: 2.0 Full Speed Current: 100 mA max File system for USB key (Flash Drive): FAT32 | |
ENVIRONMENTAL CONDI- TIONS | Indoor | Use |
Operating temperature | 0 … +50 °C (32… 122 °F) (according to IEC 68-2-14) | |
Storage temperature | -20 … +70 °C (-4…… 158 °F) (according to IEC 68-2-14) | |
Relative humidity | Max 95% RH non condensing (according to IEC 68-2-3) | |
PROTECTION RATING | IP 65 on the front (according to IEC 68-2-3) | |
ASSEMBLY | Positioning | On panel, front pull-out |
Installation requirements | Installation category: II Pollution rating: 2 Insulation: double | |
DIMENSIONS | (L × H × D) | 198 × 134.4 × 65,8 mm (7.79” x 5.29” x 6.63”) max |
WEIGHT | 0.5 kg (1.10 lb) | |
EC REGULATIONS | EMC conformity (electromagnetic compatibility) | Compliance with the 2014/30/EU Directive EMC Emission: EN 61000-6-4 EMC Immunity: EN 61131-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11 |
LV conformity (Low Voltage) | Compliance with Directive 2014/35/EU LVD safety: EN 61010-1 | |
UL REGULATIONS | Compliance with UL508 standard |
F-GCANs communications module
GENERAL DATA | ||
VOLTAGE | Operating voltage | 24 VDC ±25% |
Current absorption | 2 A max | |
Dissipated power | 2.5 W | |
Connection | Polarised connector with spring terminals, cable 1 mm2 (0.0015 in2) (17 AWG) max | |
CONNECTIONS | CAN | Connector: DB9 Protocol: CANopen 2.0B, level CAN DS301 v.3.0, v4.0 |
SIGNAL ELEMENTS | Error | Red LED |
Running | Green LED | |
Voltage | Yellow LED | |
ENVIRONMENTAL CONDI- TIONS | Indoor | Use |
Operating temperature | 0 … +55 °C (32…. 131 °F) | |
Storage temperature | -20 … +70 °C (-4…… 158 °F) | |
Relative humidity | max 95% RH non-condensing | |
PROTECTION RATING | IP20 | |
ASSEMBLY | Positioning | Vertical |
Mount | On DIN 35 mm (1.38”) rail | |
DIMENSIONS | (L × H × D) | 25.4 × 92 × 90 mm (1” x 3.62” x 3.54”) |
WEIGHT | 0.15 kg (0.33 lb) | |
EC REGULATIONS | EMC conformity (electromagnetic compatibility) | Compliance with the 2014/30/EU Directive EMC Emission: EN 61000-6-4 EMC Immunity: EN 61131-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11 |
UL REGULATIONS | Compliance with UL508 standard |
F-MIX module
INPUTS | ||||||
Number | 4 configurable + 2 by amperometric transformer | |||||
Sensor type | TC, RTD (PT100, PT1000), IR sensor, linear DC | |||||
Single-ended voltage input | Voltage: 0…10 V, 0…2,5 V | |||||
Impedance: >5 MΩ (channel 1: > 50 MΩ) | ||||||
Differential voltage input | Voltage: 0…60 mV | |||||
Impedance: >5 MΩ | ||||||
Current input | Current: 0…20 mA, 4…20 mA | |||||
Load: 100 Ω | ||||||
Potentiometer input | Potentiometer resistance: 100 Ω min. | |||||
Impedance: >5 MΩ (channel 1: > 50 MΩ) | ||||||
Extensometer input | Voltage: -5…35 mV, -10…130 mV | |||||
Impedance: > 5 MΩ | ||||||
TC input | Thermocouple: J, K, R, S, T, N, C, D, E, B, L (CJ internal) | |||||
(thermocouple) | Impedance: > 5 MΩ | |||||
RTD input | Number of wires) 2, 3 or 4 | |||||
(thermoresistance) | Thermoresistance: PT100, PT1000 | |||||
rms current: 0…50 mA RMS | ||||||
Input from a current transformer | Frequency: 50/60 Hz | |||||
Impedance: 50 Ω | ||||||
Temperature unit of measure | ° C or ° F, selectable | |||||
Probe voltage | Voltage: stabilized 10 VDC or 1 VDC, selectable | |||||
Current: 130 mA max | ||||||
Resolution | 16 bit | |||||
Input type | Number | Min | Max | Resolution | ||
Voltage 0…10 V | Number | 0 | 65535 | 0,15 mV | ||
Voltage 0…2,5 V | Number | 0 | 65535 | 0,04 mV | ||
Voltage 0…60 mV | Number | 0 | 65535 | 0,9 μV | ||
Current 0…20 mA | Number | 0 | 65535 | 0,3 μA | ||
Current 4…20 mA | Number | 13107 | 65535 | 0,3 μA | ||
Potentiometer | Number | 0 | 65535 | |||
ANALOG | Extensometer -5…35 mV | Number | 0 | 65535 | 0,6 μV | |
Extensometer | Number | 0 | 65535 | 2,14 μV | ||
-10…130 mV | ||||||
J thermocouple | °C | -210,0 | 1200,0 | 0,1 °C | ||
°F | -346 | 2192 | 0,2 °F | |||
K thermocouple | °C | -270,0 | 1372,0 | 0,1 °C | ||
°F | -454 | 2501 | 0,2 °F | |||
R thermocouple | °C | -50,0 | 1768,0 | 0,1 °C | ||
°F | 32 | 3182 | 0,2 °F | |||
S thermocouple | °C | -50,0 | 1768,0 | 0,1 °C | ||
Format and resolution | °F | -58 | 3214 | 0,2 °F | ||
T thermocouple | °C | -270,0 | 400,0 | 0,1 °C | ||
°F | -454 | 752 | 0,2 °F | |||
N thermocouple | °C | -270,0 | 1300,0 | 0,1 °C | ||
°F | -454 | 2372 | 0,2 °F | |||
C thermocouple | °C | 0,0 | 2300,0 | 0,1 °C | ||
°F | 32 | 4172 | 0,2 °F | |||
D thermocouple | °C | 0,0 | 2300,0 | 0,1 °C | ||
°F | 32 | 4523 | 0,2 °F | |||
E thermocouple | °C | -270,0 | 1000,0 | 0,1 °C | ||
°F | -454 | 1832 | 0,2 °F | |||
B thermocouple | °C | 44,0 | 1800,0 | 0,1 °C | ||
°F | 32 | 3272 | 0,2 °F | |||
L thermocouple | °C | -200,0 | 900,0 | 0,1 °C | ||
°F | -328 | 1652 | 0,2 °F | |||
RTD PT100 | °C | -200,0 | 850,0 | 0,1 °C | ||
°F | -328 | 1562 | 0,2 °F | |||
RTD PT1000 | °C | -200,0 | 850,0 | 0,1 °C | ||
°F | -328 | 1562 | 0,2 °F | |||
TA | mA | 0,0 | 50,0 | 0,01 mA |
ANALOG |
Accuracy | TC input (*) Note 1 Calibration: < ±(0,25% of value read in °C + 0,1 °C / 0,2 °F) Linearisation 1,8 % of value read Cold joint: < ±1 °C (34,7 °F) at 25 °C (77 °F) room temperature Cold joint compensation > 30:1 rejection at room temperature change
RTD input Calibration: < ±(0.15% of value read + 0.4 °C / 0,72 °F) Linearisation: 0.1% of value read Thermal shift: < ±(0.005% of the value read in °C + 0.015°C / 0,072 °F) /°C starting from 25 °C (77 °F) room temperature Linear inputs: Calibration: < 0.1% full scale Thermal shift: < ±0.005% full scale /°C starting from 25 °C (77 °F) room temperature
CT input Calibration : <0,5% full scale Thermal shift : <+/- 0,01% full scale/°C starting from 25°C (77 °F) | ||||
Conversion time | 5 ms | |||||
Protection | Polarity inversion Power surge: max 1 kV per 1 ms | |||||
Electric insulation | Channel-bus: 2.0 kV | |||||
Diagnostics | Module state: LED and software | |||||
DIGITAL | Number | 8 | ||||
Voltage | Rated: 24 VDC (according to EN 61131-2 type 1 and type 3) Max: 32 V, 10 mA | |||||
Switch limit | Low level: ≤ 8 VDC High level: ≥ 11 VDC | |||||
Protection | Polarity inversion Power surge: max 1 kV per 1 ms | |||||
Electric insulation | Channel-bus: 2.0 kV | |||||
Diagnostics | Module state: LED and software Channel state: LED and software | |||||
(*) Note 1 : for TC S valid with T>100°C; for TC B valid with T>200°C | ||||||
ANALOG | ||||||
OUTPUTS | Number | 2 | ||||
Voltage output single-ended | ±10 V, 15 mA max | |||||
Current output | 0…20 mA, 4…20 mA Max load: 600 Ω | |||||
Resolution | 16 bit | |||||
Format and resolution | Output type | Number | Min | Max | Resolution | |
±10 V | Number | -32768 | 32767 | 0.3 mV | ||
0…20 mA | Number | 0 | 32767 | 0.6 μA | ||
4…20 mA | Number | 6550 | 32767 | 0.6 μA | ||
Accuracy | Calibration precision: ±0,1% full scale @ 25 °C (77 °F) | |||||
Conversion time | 5 ms | |||||
Adjustment time | 100 μs | |||||
Protection | Short circuit: ±10 V Overload ±10 V: 16 mA max per each channel Open circuit 0…20 mA / 4…20 mA: Alarm status for open circuit Power surge: max 1 kV per 1 ms | |||||
Electric insulation | Channel-channel: No Channel-bus: 2.0 kV | |||||
Diagnostics | Module state: LED and software Channel state: LED and software |
DIGITAL | Number | 8 |
Voltage | 24 VDC ±25% | |
Current | Single output: 1 A max Total outputs: 4 A max | |
Groups | 1 group with 8 outputs | |
Protection | Short circuit Overload per output @ I ≥ 2,2 A for 500 ms min. Over temperature Power surge: max 1 kV per 1 ms | |
Electric insulation | Channel-bus: 2.0 kV | |
Diagnostics | Module state: LED and software Channel state: LED and software | |
GENERAL DATA | ||
CHANNELS | Number | 24 |
VOLTAGE | Operating voltage | 24 VDC ±25% |
Current absorption | 150 mA max | |
Dissipated power | 7.8 W | |
CONNECTIONS | Connector | Front 36 pole Wire connection with self-locking spring terminals, max cable sec- tion 0,2…1,5 mm2 (24…15 AWG) |
ENVIRONMENTAL CONDI- TIONS | Indoor | Use |
Operating temperature | 0 … +55 °C (32…. 131 °F) | |
Storage temperature | -20 … +70 °C (-4….. 158 °F) | |
Relative humidity | max 95% RH non-condensing | |
PROTECTION RATING | IP20 | |
ASSEMBLY | Positioning | Vertical |
Mount | On DIN 35 mm (1.38”) rail | |
DIMENSIONS | (L × H × D) | 25,4 × 92 × 90 mm (1” x 3.62” x 3.54”) |
WEIGHT | 0.13 kg (0.29 lb) | |
CERTIFICATIONS | CE, UL If the appropriate calibration is performed in the field, the Con- troller meets the requirements of standard AMS2750 and may be used in applications requiring the NADCAP directive |
F-EU16 module
INPUTS | ||
DIGITAL | Number | 8 |
Voltage | Rated: 24 VDC (according to EN 61131-2 type 1 and type 3) Max: 32 V, 25 mA | |
Switch limit | Low level: ≤ 8 VDC High level: ≥ 11 VDC | |
Filter | Hardware: 100 Hz or 5 kHz selectable from software | |
Protection | Polarity inversion Power surge: max 1 kV per 1 ms | |
Electric insulation | Channel-bus: 2.0 kV | |
Diagnostics | Module state: LED and software Channel state: LED and software | |
ANALOG | ||
DIGITAL | Number | 8 |
Groups | 2 group with 4 outputs | |
Voltage | 24 VDC ±25% | |
Current | Single output: 2 A max Single group: 5 A max Total outputs: 8 A max | |
Protection | Short circuit Overload per output @ I ≥ 2,2 A for 500 ms min. Over temperature Power surge: max 1 kV per 1 ms | |
Electric insulation | Channel-bus: 2.0 kV | |
Diagnostics | Module state: LED and software Channel state: LED and software | |
GENERAL DATA | ||
CHANNELS | Number | 16 |
VOLTAGE | Operating voltage | 24 VDC ±25% |
Current absorption | 8 A max | |
Dissipated power | 9 W | |
CONNECTIONS | Connector | Front 26 pole Wire connection with self-locking spring terminals, max cable sec- tion 0,2…1.5 mm2 (24…15 AWG) |
ENVIRONMENTAL CONDI- TIONS | Indoor | Use |
Operating temperature | 0 … +55 °C (32…. 131 °F) | |
Storage temperature | -20 … +70 °C (-4….. 158 °F) | |
Relative humidity | max 95% RH non-condensing | |
PROTECTION RATING | IP20 | |
ASSEMBLY | Positioning | Vertical |
Mount | On DIN 35 mm (1.38”) rail | |
DIMENSIONS | (L × H × D) | 25.4 × 92 × 90 mm (1” x 3.62” x 3.54”) |
WEIGHT | 0.13 kg (0.29 lb) | |
CERTIFICATIONS | CE, UL |
Reviews