Description
TECHNICAL DATA OF HiC2441
General specifications | ||
---|---|---|
Signal type | Universal | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) | |
Rated voltage | 19 … 30 V DC via Termination Board | |
Ripple | ≤ 10 % | |
Rated current | ≤ 30 mA | |
Power consumption | ≤ 700 mW | |
Analog input | ||
Suitable field devices | 2-wire SMART transmitters, current sources | |
Signal | 0/4 … 20 mA , limited to approx. 40 mA (depends on control system) , reverse polarity protected | |
Field circuit | SL2: 5a(+), 5b(-) (2-wire SMART transmitter) SL2: 5a(+), 1b(-) (2-wire SMART transmitter with current source) | |
Voltage drop | approx. 4 V (current source) | |
Control circuit | SL1: 8a(+), 7a(-) | |
Supply voltage | min. 16 V at 20 mA (2-wire SMART transmitter) | |
Voltage | 15 … 30 V | |
Signal | 0/4 … 20 mA , sink mode , working voltage 15 … 30 V | |
Ripple | 20 mV rms | |
Analog output | ||
Suitable field devices | I/P converters (positioner), on-site-displays | |
Signal | 0/4 … 20 mA | |
Field circuit | SL2: 5a(+), 5b(-) | |
Load | 0 … 650 Ω | |
Voltage | ≥ 13 V at 20 mA | |
Ripple | 20 mV rms | |
Control circuit | SL1: 8a(+), 7a(-) | |
Voltage | 12 … 30 V | |
Signal | 0/4 … 20 mA | |
Line fault detection | > 100 kΩ at max. 30 V, with field wiring open | |
Digital input | ||
Field circuit | SL2: 5a(+), 1a(-) (NAMUR sensor) SL2: 5a(+), 5b(-) (dry contact) | |
Suitable field devices | NAMUR sensors according to IEC/EN 60947-5-6, dry contacts | |
Signal | 0.1 … 9 mA , sink mode | |
Open loop voltage | approx. 10 V DC , 1 kΩ series resistance | |
Signal | 0.1 … 9 mA | |
Control circuit | SL1: 8a(+), 7a(-) | |
Voltage | 13 … 30 V | |
Digital output | ||
Field circuit | SL2: 5a(+), 5b(-) | |
Suitable field devices | solenoid valves, acoustic or visual alarms | |
Drive capability | 12 V / 40 mA at 300 Ω load | |
Open loop voltage | approx. 22 V | |
Current limit | 45 mA | |
Internal resistor | min. 240 Ω | |
Control circuit | SL1: 8a(+), 7a(-) | |
Voltage | 1-signal: 19 … 30 V DC 0-signal: 0 … 5 V DC | |
Current | 1-signal: 0 … 45 mA, depending on the output load 0-signal: < 0.1 mA, independent of the output load | |
Power dissipation | 1.1 W at 24 V, 300 Ω load (digital output) | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F) ≤ ±20 µA incl. linearity, hysteresis and supply fluctuations at 4 … 20 mA (analog input, analog output) ≤ ±60 µA incl. linearity, hysteresis and supply fluctuations at 0 … 45 mA (digital output) | |
Influence of ambient temperature | < 2 µA/K (0 … 70 °C (32 … 158 °F)) < 3 µA/K (-40 … 0 °C (-40 … 32 °F)) | |
Switching frequency | ≤ 500 Hz with 50 % duty cycle (digital input, NAMUR sensor) ≤ 5 Hz (digital input, dry contact) ≤ 20 Hz (digital output) | |
Frequency range | HART: bandwidth by 0.5 Vpp signal and/or 1 mApp signal 950 … 2500 Hz (analog input, analog output) | |
Settling time | ≤ 20 ms (analog input, analog output) ≤ 1 ms (digital input, NAMUR sensor) | |
Reaction time | ≤ 5 ms , turn-on/turn-off time (digital output) | |
Galvanic isolation | ||
Control/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | IEC 61010-1:2010 | |
Input | EN 60947-5-6:2000 | |
Ambient conditions | ||
Ambient temperature | -40 … 70 °C (-40 … 158 °F) Observe the temperature range limited by derating, see section derating. | |
Storage temperature | -40 … 85 °C (-40 … 185 °F) | |
Relative humidity | 95 % non-condensing | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) | |
Mounting | on Termination Board | |
Coding | pin 1 and 4 trimmed For further information see system description. | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | TÜV 14 ATEX 153522 X | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
Supply | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Equipment | SL2: 5a(+), 5b(-) | |
Voltage Uo | 25.2 V | |
Current Io | 110 mA | |
Power Po | 693 mW | |
Internal capacitance Ci | 5.7 nF | |
Internal inductance Li | 0 mH | |
Equipment | SL2: 5a(+), 1b(-) | |
Voltage Ui | < 28 V | |
Current Ii | < 115 mA | |
Voltage Uo | 7.2 V | |
Current Io | 0 mA | |
Power Po | 0 mW | |
Internal capacitance Ci | 5.7 nF | |
Internal inductance Li | 0 mH | |
Equipment | SL2: 5a(+), 1a(-) | |
Voltage Uo | 12.6 V | |
Current Io | 13 mA | |
Power Po | 41 mW | |
Internal capacitance Ci | 5.7 nF | |
Internal inductance Li | 0 mH | |
Certificate | TÜV 14 ATEX 153523 X | |
Marking | II 3G Ex ec IIC T4 Gc | |
Galvanic isolation | ||
Input/Other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015 | |
International approvals | ||
UL approval | E106378 | |
Control drawing | 116-0408 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx TUN 15.0004X | |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
---|---|
ECLASS 11.0 | 27210107 |
ECLASS 10.0.1 | 27210107 |
ECLASS 9.0 | 27210107 |
ECLASS 8.0 | 27210107 |
ECLASS 5.1 | 27210107 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
Reviews
There are no reviews yet.