Mô tả
THÔNG SỐ KỸ THUẬT CỦA HiC5861Y1
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Performance level (PL) | PL e | |
Supply | ||
Connection | loop powered | |
Rated voltage | 19 … 30 V DC loop powered | |
Power dissipation | < 1.3 W | |
Power consumption | < 1.3 W | |
Input | ||
Connection side | control side | |
Connection | Input SL1: 8a(+), 7a(-) ; test input SL1: 3a(-), 3b(+), 4a(+), 4b(+) | |
Pulse/Pause ratio | 150 ms / 150 ms | |
Test pulse length | max. 4 ms from DO card | |
Test input | see Functional Safety Manual | |
Signal level | 0-signal: -5 … 5 V 1-signal: 19 … 27.6 V | |
Rated voltage | 19 … 27.6 V loop powered | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | SL2: 5a, 7a; 1a, 3a | |
Contact loading | 253 V AC/2 A/cos φ 0,7; 30 V DC/2 A resistive load | |
Minimum switch current | 10 mA / 24 V DC | |
Energized/De-energized delay | 150 ms / 150 ms | |
Mechanical life | 2 x 107 switching cycles | |
Fuse rating | 3.15 A | |
Transfer characteristics | ||
Switching frequency | < 3 Hz | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 253 Veff | |
Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 253 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Machinery Directive | ||
Directive 2006/42/EC | EN 62061:2005 , EN/ISO 13849-1:2008 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 … 60 °C (-4 … 140 °F) Observe the temperature range limited by derating, see section derating. | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 128 x 106 mm (0.5 x 5.1 x 4.2 inch) | |
Mounting | on Termination Board | |
Coding | no pin trimmed For further information see system description. | |
Data for application in connection with hazardous areas | ||
Certificate | PF 17 CERT 4312 X | |
Marking | II 3G Ex nC ec IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
---|---|
ECLASS 11.0 | 27210101 |
ECLASS 10.0.1 | 27210101 |
ECLASS 9.0 | 27210101 |
ECLASS 8.0 | 27210101 |
ECLASS 5.1 | 27210121 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
Đánh giá
Chưa có đánh giá nào.